Return to Order Page
Duct Construction Standards: 2" Water Gauge
Material: Galvanized
Sealer: Joint Connections
Seams: 24-26 ga. Snaplock, 18-22 ga. Pittsburgh
D Drive (24 ga.) |
SD Standing Drive (22 ga.) |
S S-lock (24 ga.) |
SS Standing S-lock |
TDC Transverse Duct Connector |
IRA Intermediate Reinforcing Angle |
MPT Midpoint Tie Rod |
JTR Joint Tie Rod |
Duct Size
|
Gauge
|
Connection Joint
|
Reinforcement
|
Centers
|
Major
|
Minor
|
10" & dn
|
26
|
59"
|
S
|
D
|
None
|
11" - 14"
|
26
|
59"
|
SS
|
SD
|
None
|
15" - 20"
|
24
|
59"
|
SS
|
SD
|
None
|
21" - 30"
|
24
|
56"
|
TDC
|
TDC
|
None
|
31" - 36"
|
22
|
56"
|
TDC
|
TDC
|
None
|
37" - 42"
|
24
|
56"
|
TDC
|
TDC
|
MPT
|
43" - 54"
|
22
|
56"
|
TDC
|
TDC
|
MPT
|
55" - 84"
|
22
|
56"
|
TDC
|
TDC
|
JTR (2)MPT
|
85" - 96"
|
20
|
56"
|
TDC
|
TDC
|
JTR (2)MPT
|
97" - 120"
|
18
|
56"
|
TDC
|
TDC
|
JTR/MPT/IRA (2 1/2 x 1/8)
|
(1) Based upon 1995 SMACNA HVAC Duct Construction Standards.
(2) Install tie rods (JTR & MPT) at 60" spacing for ducts over 120" wide.
(3) All duct beaded or crossbroken.
(4) Fittings and duct reinforced alike.
(5) JTR's required on both sides of joint.
(6) Refer to job specifications for specific sealer requirements.